题名: |
Seismic Fragility Study of Fire Sprinkler Piping Systems with Grooved Fit Joints |
其他题名: |
American Society of Civil Engineers(ASCE).(2010)."Minimum design loads for buildings and other structures."ASCE/SEI 7-10,Reston,VA. |
正文语种: |
英文 |
作者: |
Siavash Soroushian |
关键词: |
parameter;relationship;joint;groove;component;systems;thread;fire;agil;level |
摘要: |
A comprehensive analytical model is developed for a pressurized fire sprinkler piping system of a hospital building. A suite of ninety-six artificial triaxial floor acceleration histories is used to generate seismic fragility parameters of the sprinkler piping system. The analytical model accounts for the inelastic behavior of braces, hangers, and wire restrainers. It incorporates an experimentally validated hysteresis model developed, as part of this study, for the moment-rotation relationship of grooved fitted joints. Component fragility parameters were obtained for lateral restrainers, hangers, and pipe joints. Three system-level damage states were defined based on the level of functionality of fire sprinkler systems and severity of leakage after a seismic event and a joint probabilistic model were utilized to obtain system-level fragility parameters. Finally, the seismic fragility of fire sprinkler systems with grooved fit joints is compared to that of a piping system with threaded joints. |
出版年: |
2015 |
论文唯一标识: |
P-26Y2015V141N06010 |
英文栏目名称: |
Technical Papers |
doi: |
10.1061/(ASCE)ST.1943-541X.0001122 |
期刊名称: |
Journal of Structural Engineering |
拼音刊名(出版物代码): |
P-26 |
卷: |
141 |
期: |
06 |
页码: |
97-111 |